Industrial Dry Chemical System

The NFPA 17 standard requires the maintenance of dry chemical fire suppression equipment in good working order along with inspection, testing and maintenance records. Inspections will be performed on a semi-annual basis.

Examples of work performed during an inspection include:
    • Complete visual inspection to determine the type of components used in the system and conduct verification of the same.
    • Complete the system function test to confirm the system is functioning as designed and per the manufacturer’s recommendations, including manual and automatic activation.
    • Check the tank pressure, the cylinder test dates and the overall condition of the system tank, control head, and components.
    • Verify that all the appropriate shutdowns take place, the building’s fire alarm system is activated and that all nozzles are clean and unobstructed.
    • Upon completion of the inspection and performing any necessary repairs, the applicable inspection documents and noted deficiencies shall be left at the location and made available electronically.
    • Tag all devices as required and perform required record keeping.